Title : Analysis
of Neutral Current during Impulse Test of 400 kV Transformers using Coherence
Function
Author
Name : SHASHIDHAR REDDY, M P V
V R Kumar , B.P.Singh , M.Surya Kalavathi
Synopsis :
Several authors have published work related to
detection of fault in high voltage transformers using Sweep Frequency Response
Analysis (SFRA), Wavelet and Coherence. The work published in this paper
describes the result of analysis of neutral current during reduced and full
impulse voltage test of 400 KV transformers with detailed analysis using
Coherence Function (CF). It is aimed at determining the variation of CF due to
change in neutral current for transformers which have either passed or failed
during certification test. In order to establish criteria, theoretical
simulation was carried out initially to determine the nature of CF for different
types of noise superimposed on impulse wave. The analysis was done for high
voltage transformer by recording neutral current during calibration and full
impulse voltage test of high voltage winding, using data obtained during
testing. Of the three types of transformers, two have passed the test and one
has encountered major failure. For the purpose of analysis the two outputs i.e.
neutral currents at reduced and full voltage with appropriate scaling were
used. The assumption is made that for similar inputs, outputs must remain
similar as long as the equivalent electric circuit remains unchanged. In the
event of any change by way of fault, electromagnetic interference and jitter,
the CF is likely to be less than unity.